162
Monitoring
Chapter 11
Verifying settings by secondary
injection
Table 22:
Test settings
14.3.1
Measuring the operate limit
Procedure
1.
Set the test point (|Z| fault impedance and Z
Φ
impedance phase
angle ) for a condition that meets the requirements in
.
2.
Subject the IED to healthy normal load conditions for at least two
seconds.
3.
Apply a fault condition.
Check that the distance-to-fault value displayed on the HMI complies
with the following equations (the error should be less than five percent):
in % for two- and three-phase faults
in % for single-phase-to-earth faults
in % for single-phase-to-earth faults with mutual zero sequence current.
Parameter:
Condition:
I
Higher than 30% I
r
Healthy conditions
U = 63,5 V, I = 0 A & ZF = 0
°
Impedance |Z|
Test point
Note:
•
Z
x
≤
(X0 + 2 · X1)/3For single-phase faults
•
Z
x
≤
X1 For three and two phase faults
•
Z
x
≤
(X0 + 2 · X1 XM)/3For single-phase fault with mutual
zero-sequence current
Impedance angle Z
Φ
Test angle
•
Z
Φ
arctan[(X0 + 2 · X1) / (R0 + 2R1)] For single-phase faults
•
Z
Φ
arctan(X1/R1)For two-phase faults
Where:
p
= the expected value of a distance to fault in percent
Z
x
= set test point on the test set
X0
= set zero-sequence reactance of a line
X1
= set positive-sequence reactance of a line
XM
= set mutual zero-sequence impedance of a line
p
Z
x
X1
-------
100
⋅
=
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...