5 Installation and Commissioning
5.4 Robot Safety System Connections
68
Product Manual, Control Cabinet IRC5P
section
’External Emergency Stop (Category 0)’
on page 70. This type of
emergency stop is included in the emergency stop chain and is typically used in
a simple robot installation.
The emergency stop chain can also be implemented in the plant’s emergency
stop chain. For information on this connection, see
3.
Install Auto Mode Stop (Category 0) switch to prevent people from entering the
robot working area while the robot is in operation. For connection information,
see section
4.
If the Robot’s emergency stop system is to be implemented in the plant’s
emergency stop system, General Mode Stop (Category 0) or Delayed Stop
(Category 1) in the Run Chain may be used instead of the ‘normal’ Emergency
Stop function. For information on this connection, see section
on page 74, alternatively
5.
If required, install External Emergency Stop Reset Button(s) or connect reset
input to the plants emergency stop system controller. For information on these
connections, see section
6.
If required, implement an Extra Enabling Device in addition to the enabling
device on the pendant. For information, see section
7.
If required, install Cabin Safety Switches. These functions can be used to
disable functions such as fluid pumps, spray-gun, bell, electrostatic high
voltage etc. for safety reasons. For information on these connections, see
section
Содержание IRC5P
Страница 1: ...The heart of Robotics Product Manual Control Cabinet IRC5P 3HNA009834 001 en Rev 06 ...
Страница 2: ......
Страница 10: ...10 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 14: ...2 Safety 14 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 30: ...3 System Description 3 4 Pendant Description 30 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 218: ...218 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P Manual Status ...