8 Trouble Shooting
8.5 LED Indicator Panel
204
Product Manual, Control Cabinet IRC5P
MISC.
LEDs showing status of the LED board and LEDs which can be defined by the user.
Description
Source of fault / Remedy
USER
4 + 3 user definable LEDs.
These LEDs can be specified by the user in the software.
Display Valid
Green - OK. System indicator
board, ALED is active.
Off - ALED board not active.
Note that LED is blinking red/green
during initialization until
communication with PIB is started.
– Check communication cable between PIB and ALED.
– Try to reset board by momentary disconnecting power
connector to ALED.
– Check ALED board. Replace board as required.