5 Installation and Commissioning
5.8 Power Connections
118
Product Manual, Control Cabinet IRC5P
5.8.4 Supply for Internal Light
General
The controller may include a connection for a single phase 115/230 VAC for
internal light. This supply can also be used to supply an optional cooler unit.
The internal light includes a rectifier which makes it operate on supply voltages
from 90V to 250V.
Specification
Connections
The external 115 or 230 VAC is connected to terminal board XT1.1, located beside
the mains overload protection, FR1, in the lower left bottom of the control cabinet
. The AC power is connected to the rectifier via a door switch.
The light is switched on when the cabinet door is open.
Figure 61 115/230 VAC terminal board
Optionally the power may be connected to the control cabinet internal power
supply, which means that the light can only be switched on when the control cabinet
is switched on.
For information on tightening torque for terminal connections, see
For connection for cooler, see
Voltage
115 or 230 V
Supply line fuses
Max. 10A
Mains overload
protection, FR1
Factory 115/230 VAC supply
L
N
P
.E
Optional cooler
Internal light
Rectifier
Door switch
Normal Closed
when door open
X78
XT1.1
Содержание IRC5P
Страница 1: ...The heart of Robotics Product Manual Control Cabinet IRC5P 3HNA009834 001 en Rev 06 ...
Страница 2: ......
Страница 10: ...10 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 14: ...2 Safety 14 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 30: ...3 System Description 3 4 Pendant Description 30 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 218: ...218 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P Manual Status ...