5 Installation and Commissioning
5.7 Misc. System Connections
106
Product Manual, Control Cabinet IRC5P
Installation Procedure
This procedure describes how to install the cooler on the control cabinet.
If the cooler is ordered together with the robot and control cabinet, the cooler is
already installed and this installation procedure can be skipped. Continue with
1.
Remove cooler from box. Be careful when lifting cooler.
2.
Remove paper on gasket adhesive surface. Place gasket on cabinet mounting
surface with adhesive side facing cabinet. Pay attention to get gasket correctly
positioned.
3.
Place cooler on its side and install 8 supplied headless screws.
4.
Open cabinet front door. Lift cooler onto side of cabinet. Guide headless screws
into attachment holes.
5.
Install washers and nuts on screws from inside cabinet. Tighten nuts.
6.
As the air inside the cabinet is cooled down, condensation arises in the cooler. It
is therefore important to make an arrangement as shown in the illustration to
lead the condensate from the cooler to the outside of the cabinet.
Important:
To minimize condensation, it is important to set the internal temperature
(default 38°C) not lower than actually needed. To prevent condensation inside the
control cabinet, ensure that the control cabinet is a sealed enclosure, especially
watch cable inlets and door seals.
7.
Install door switch. Cooling is switched off when control cabinet door is open.
8.
Install connector X79 and terminal X78. The external 115 or 230 VAC is
connected to terminal board XT1.1, located beside the mains overload
protection, FR1, in the lower left bottom of the controller as shown in
. See also
9.
Insert electrical connector of the cooler into X79.
Installation Checks
After the installation has been performed, and if the cooler has been installed before
shipment, it is important to check the following:
– To prevent condensation inside the control cabinet, ensure that the control
cabinet is a sealed enclosure, especially watch cable inlets and door seals.
– Ensure that the condensate from the cooler is lead to the outside of the control
cabinet.
– Ensure that the door switch is open when the control cabinet door is open. To
minimize condensation inside the control cabinet, cooling is switched off when
control cabinet door is open.
Содержание IRC5P
Страница 1: ...The heart of Robotics Product Manual Control Cabinet IRC5P 3HNA009834 001 en Rev 06 ...
Страница 2: ......
Страница 10: ...10 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 14: ...2 Safety 14 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 30: ...3 System Description 3 4 Pendant Description 30 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P ...
Страница 218: ...218 3HNA009834 001 en Rev 06 Product Manual Control Cabinet IRC5P Manual Status ...