ACQ550-U1 User’s Manual
67
Application macros
Macro default values for parameters
Parameter default values are listed in section
on page
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
Note:
Configured for 60 Hz/NEMA compliance (ACQ550-U1).
ACQ550-U1
Parameter
ABB 2-wire
3-wire
Alternate
Motor
Potentio-
meter
Hand-auto PID Control PFC Control
9902
APPLIC
MACRO
1 =
ABB
STANDARD
2 =
3-
WIRE
3 =
ALTERNATE
4 =
MOTOR
POT
5 =
HAND
/
AUTO
6 =
PID
CONTROL
7 =
PFC
CONTROL
9904
MOTOR
CTRL
MODE
3 =
SCALAR
:
FREQ
1 =
VECTOR
:
SPEED
1 =
VECTOR
:
SPEED
1 =
VECTOR
:
SPEED
1 =
VECTOR
:
SPEED
1 =
VECTOR
:
SPEED
3 =
SCALAR
:
FREQ
1001
EXT
1
COMMANDS
2 =
DI
1,2
4 =
DI
1
P
,2
P
,3 9 =
DI
1
F
,2
R
2 =
DI
1,2
2 =
DI
1,2
1 =
DI
1
1 =
DI
1
1002
EXT
2
COMMANDS
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
7 =
DI
6,5
6 =
DI
6
6 =
DI
6
1003
DIRECTION
3 =
REQUEST
3 =
REQUEST
3 =
REQUEST
3 =
REQUEST
3 =
REQUEST
1 =
FORWARD
1 =
FORWARD
1102
EXT
1/
EXT
2
SEL
0 =
EXT
1
0 =
EXT
1
0 =
EXT
1
0 =
EXT
1
3 =
DI
3
2 =
DI
2
3 =
DI
3
1103
REF
1
SELECT
1 =
AI
1
1 =
AI
1
1 =
AI
1
12 =
DI
3
U
,4
D
(
NC
)
1 =
AI
1
1 =
AI
1
1 =
AI
1
1106
REF
2
SELECT
2 =
AI
2
2 =
AI
2
2 =
AI
2
2 =
AI
2
2 =
AI
2
19 =
PID
1
OUT
19 =
PID
1
OUT
1201
CONST
SPEED
SEL
9 =
DI
3,4
10 =
DI
4,5
9 =
DI
3,4
5 =
DI
5
0 =
NOT
SEL
9 =
DI
3,4
0 =
NOT
SEL
1304
MINIMUM
AI
2
0.0%
0.0%
0.0%
0.0%
20.0%
20.0%
20.0%
1401
RELAY
OUTPUT
1
1 =
READY
1 =
READY
1 =
READY
1 =
READY
1 =
READY
1 =
READY
2 =
RUN
1402
RELAY
OUTPUT
2
2 =
RUN
2 =
RUN
2 =
RUN
2 =
RUN
2 =
RUN
2 =
RUN
3 =
FAULT
(-1)
1403
RELAY
OUTPUT
3
3 =
FAULT
(-1)
3 =
FAULT
(-1) 3 =
FAULT
(-1) 3 =
FAULT
(-1) 3 =
FAULT
(-1) 3 =
FAULT
(-1) 31 =
PFC
1501
AO
1
CONTENT
SEL
103 = 0103
OUTPUT
FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT
FREQ
1507
AO
2
CONTENT
SEL
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
130 =
PID
1
FBK
1510
MINIMUM
AO
2
0.0 mA
0.0 mA
0.0 mA
0.0 mA
0.0 mA
0.0 mA
4.0 mA
1601
RUN
ENABLE
0 =
NOT
SEL
0 =
NOT
SEL
6 =
DI
6
6 =
DI
6
4 =
DI
4
5 =
DI
5
2 =
DI
2
2201
ACC
/
DEC
1/2
SEL
5 =
DI
5
0 =
NOT
SEL
5 =
DI
5
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
3201
SUPERV
1
PARAM
103 = 0103
OUTPUT
FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT
FREQ
3401
SIGNAL
1
PARAM
103 = 0103
OUTPUT
FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT
FREQ
4001
GAIN
1.0
1.0
1.0
1.0
1.0
1.0
2.5
4002
INTEGRATION
TIME
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
3.0 s
4101
GAIN
1.0
1.0
1.0
1.0
1.0
1.0
2.5
4102
INTEGRATION
TIME
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
3.0 s
8123
PFC
ENABLE
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
1 =
ACTIVE
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...