ACQ550-U1 User’s Manual
211
Embedded fieldbus
DCU profile
STATUS
WORD
(See parameter 0304)
Bit
Name
Value
Status
16
ALARM
1
An alarm is on.
0
No alarms are on.
17
REQ_MAINT
1
A maintenance request is pending.
0
No maintenance request is pending.
18
DIRLOCK
1
Direction lock is ON. (Direction change is locked out.)
0
Direction lock is OFF.
19
LOCALLOCK
1
Local mode lock is ON. (Local mode is locked out.)
0
Local mode lock is OFF.
20
CTL_MODE
1
Drive is in vector control mode.
0
Drive is in scalar control mode.
21…25
Reserved
26
REQ_CTL
1
Copy the control word
0
(no op)
27
REQ_REF1
1
Reference 1 requested in this channel.
0
Reference 1 is not requested in this channel.
28
REQ_REF2
1
Reference 2 requested in this channel.
0
Reference 2 is not requested in this channel.
29
REQ_REF2EXT
1
External PID reference 2 requested in this channel.
0
External PID reference 2 is not requested in this channel.
30
ACK_STARTINH
1
A start inhibit from this channel is granted.
0
A start inhibit from this channel is not granted.
31
ACK_OFF_ILCK
1
Start inhibit due to OFF button
0
Normal operation
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...