74
ACQ550-U1 User’s Manual
Parameters
2113
START
DELAY
0.00…60.00 s
0.01 s
0.00 s
Group 22: ACCEL/DECEL
2201
ACC
/
DEC
1/2
SEL
-6…7
1
0 (
NOT
SEL
)
2202
ACCELER
TIME
1
0.0…1800.0 s
0.1 s
5.0 s
2203
DECELER
TIME
1
0.0…1800.0 s
0.1 s
5.0 s
2204
RAMP
SHAPE
1
0.0 =
LINEAR
, 0.1…1000.0 s
0.1 s
0.0 s
2205
ACCELER
TIME
2
0.0…1800.0 s
0.1 s
60.0 s
2206
DECELER
TIME
2
0.0…1800.0 s
0.1 s
60.0 s
2207
RAMP
SHAPE
2
0.0 =
LINEAR
, 0.1…1000.0 s
0.1 s
0.0 s
2208
EMERG
DEC
TIME
0.0…1800.0 s
0.1 s
1.0 s
2209
RAMP
INPUT
0
-6…7
1
0 (
NOT
SEL
)
Group 23: SPEED CONTROL
2301
PROP
GAIN
0.00…200.00
0.01
5.00
2302
INTEGRATION
TIME
0.00…600.00 s
0.01 s
0.50 s
2303
DERIVATION
TIME
0…10000 ms
1 ms
0 ms
2304
ACC
COMPENSATION
0.00…600.00 s
0.01 s
0.00 s
2305
AUTOTUNE
RUN
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
Group 25: CRITICAL SPEEDS
2501
CRIT
SPEED
SEL
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
2502
CRIT
SPEED
1
LO
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2503
CRIT
SPEED
1
HI
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2504
CRIT
SPEED
2
LO
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2505
CRIT
SPEED
2
HI
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2506
CRIT
SPEED
3
LO
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2507
CRIT
SPEED
3
HI
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
Group 26: MOTOR CONTROL
2601
FLUX
OPT
ENABLE
0 =
OFF
, 1 =
ON
1
1 (
ON
)
2602
FLUX
BRAKING
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
2603
IR
COMP
VOLT
0.0…100.0 V
0.1 V
Size dependent
2604
IR
COMP
FREQ
0…100%
1%
80%
2605
U
/
F
RATIO
1 =
LINEAR
, 2 =
SQUARED
1
2 (
SQUARED
)
2606
SWITCHING
FREQ
1, 2, 4, 8, 12 kHz
-
4 kHz
2607
SWITCH
FREQ
CTRL
0 =
OFF
, 1 =
ON
1
1 (
ON
)
2608
SLIP
COMP
RATIO
0…200%
1%
0%
2609
NOISE
SMOOTHING
0 =
DISABLE
, 1 =
ENABLE
1
0 (
DISABLE
)
2619
DC
STABILIZER
0 =
DISABLE
, 1 =
ENABLE
1
0 (
DISABLE
)
2625
OVERMODULATION
0 =
DISABLE
, 1 =
ENABLE
1
0 (
DISABLE
)
2627
FLUX
STAB
GAIN
0...5000
1
100
2628
DC
STAB
GAIN
0...2000
1
25
Group 29: MAINTENANCE TRIG
2901
COOLING
FAN
TRIG
0.0…6553.5 kh, 0.0 disables
0.1 kh
0.0 kh
2902
COOLING
FAN
ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
2903
REVOLUTION
TRIG
0…65535 Mrev, 0 disables
1 Mrev
0 Mrev
2904
REVOLUTION
ACT
0…65535 Mrev
1 Mrev
0 Mrev
2905
RUN
TIME
TRIG
0.0…6553.5 kh, 0.0 disables
0.1 kh
0.0 kh
Code
Name
Range
Resolution
Default
User
S
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...