208
ACQ550-U1 User’s Manual
Embedded fieldbus
Status Word
The contents of the
STATUS
WORD
is status information, sent by the drive to the
master station.
8
STPMODE_EM
1
Emergency ramp
stop mode
0
(no op)
9
STPMODE_C
1
Coast stop mode
0
(no op)
10
RAMP_2
1
Ramp pair 2
0
Ramp pair 1
11
RAMP_OUT_0
1
Ramp output to 0
0
(no op)
12
RAMP_HOLD
1
Ramp freeze
0
(no op)
13
RAMP_IN_0
1
Ramp input to 0
0
(no op)
14
RREQ_LOCALL
OC
1
Local mode lock
In lock, drive will not switch to local mode.
0
(no op)
15
TORQLIM2
1
Torque limit pair 2
0
Torque limit pair 1
DCU profile
CONTROL
WORD
(See parameter 0302)
Bit
Name
Value
Function
Comments
16…26
Reserved
27
REF_CONST
1
Constant speed ref. These bits are only for supervision
purposes.
0
(no op)
28
REF_AVE
1
Average speed ref.
0
(no op)
29
LINK_ON
1
Master is detected
in link
0
Link is down
30
REQ_STARTINH
1
Start inhibit request
is pending
0
Start inhibit request
is OFF
31
OFF_INTERLOCK
1
Panel OFF button
pressed
For the control panel (or PC tool) this is
the OFF button interlock.
0
(no op)
DCU profile
CONTROL
WORD
(See parameter 0301)
Bit
Name
Value
Command/Req.
Comments
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...