ACQ550-U1 User’s Manual
173
5 =
DI
5 – Enables the Interlock function and assigns a digital input (starting with
DI
5) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
• the number of PFC relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFC
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0.0, and otherwise enabled).
6 =
DI
6 – Enables the Interlock function and assigns digital input
DI
6 to the interlock signal for the speed regulated
motor.
• Requires 8118
AUTOCHNG
INTERV
= 0.0.
Code Description
No. PFC
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1…
DI
4: Free
DI
5: Speed Reg Motor
DI
6: Free
Not allowed
1
DI
1…
DI
4: Free
DI
5: Speed Reg Motor
DI
6: First PFC Relay
DI
1…
DI
4: Free
DI
5: First PFC Relay
DI
6: Free
2
Not allowed
DI
1…
DI
4: Free
DI
5: First PFC Relay
DI
6: Second PFC Relay
3…6
Not allowed
Not allowed
No. PFC
relays
Autochange disabled
Autochange enabled
0
DI
1…
DI
5: Free
DI
6: Speed Reg Motor
Not allowed
1
Not allowed
DI
1…
DI
5: Free
DI
6: First PFC Relay
2…6
Not allowed
Not allowed
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...