ACQ550-U1 User’s Manual
175
8124
ACC IN AUX STOP
Sets the PFC acceleration time for a zero-to-maximum
frequency ramp. This PFC acceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched off.
• Replaces the acceleration ramp defined in
.
• Applies only until the output of the regulated motor
increases by an amount equal to the output of the
switched off auxiliary motor. Then the acceleration ramp
defined in
applies.
0 =
NOT
SEL
.
0.1…1800 – Activates this function using the value
entered as the acceleration time.
• A = speed regulated motor accelerating using
parameters (2202 or 2205).
• B = speed regulated motor decelerating using
parameters (2203 or 2206).
• At aux. motor start, speed regulated motor decelerates
using 8125
DEC
IN
AUX
START
.
• At aux. motor stop, speed regulated motor accelerates
using 8124
ACC
IN
AUX
STOP
.
8125
DEC IN AUX START
Sets the PFC deceleration time for a maximum-to-zero
frequency ramp. This PFC deceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched on.
• Replaces the deceleration ramp defined in
.
• Applies only until the output of the regulated motor
decreases by an amount equal to the output of the
auxiliary motor. Then the deceleration ramp defined in
applies.
0 =
NOT
SEL
.
0.1…1800 – Activates this function using the value
entered as the deceleration time.
8126
TIMED AUTOCHNG
Sets the autochange using a Timed function. See parameter 8119
AUTOCHNG
LEVEL
.
0 =
NOT
SEL
.
1 =
TIMED
FUNC
1 – Enables autochange when Timed function 1 is active.
2…4 =
TIMED
FUNC
2…4 – Enables autochange when Timed function 2…4 is active.
8127
MOTORS
Sets the actual number of PFC controlled motors (maximum 7 motors, 1 speed regulated, 3 connected direct-on-line
and 3 spare motors).
• This value includes also the speed regulated motor.
• This value must be compatible with the number of relays allocated to PFC if the Autochange function is used.
• If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to
PFC but it needs to be included in this value.
8128
AUX START ORDER
Sets the start order of the auxiliary motors.
1 =
EVEN
RUNTIME
– Time sharing is active. Evens out the cumulative run time of the auxiliary motors. The start order
depends on the run time: The auxiliary motor whose cumulative run time is shortest is started first, then the motor
whose cumulative run time is the second shortest etc. When the demand drops, the first motor to be stopped is the
one whose cumulative run time is longest.
2 =
RELAY
ORDER
– The start order is fixed to be the order of the relays.
Code Description
P 8125
P 8124
A
B
1
0
Aux.
motor
f
OUT
t
t
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...