ACQ550-U1 User’s Manual
119
2304
ACC COMPENSATION
Sets the derivation time for acceleration compensation.
• Adding a derivative of the reference to the output of the speed controller compensates for inertia during
acceleration.
• 2303
DERIVATION
TIME
describes the principle of derivative action.
• Rule of thumb: Set this parameter between 50 and 100% of the sum of the mechanical time constants for the motor
and the driven machine.
• The figure shows the speed responses when a high inertia load is accelerated along a ramp.
*Note:
You can use parameter 2305
AUTOTUNE
RUN
to automatically set acceleration compensation.
2305
AUTOTUNE RUN
Starts automatic tuning of the speed controller.
0 =
OFF
– Disables the Autotune creation process. (Does not disable the operation of Autotune settings.)
1 =
ON
– Activates speed controller autotuning. Automatically reverts to
OFF
.
Procedure:
Note:
The motor load must be connected.
• Run the motor at a constant speed of 20 to 40% of the rated speed.
• Change the autotuning parameter 2305 to
ON
.
The drive:
• Accelerates the motor.
• Calculates values for proportional gain, integration time and acceleration compensation.
• Changes parameters 2301, 2302 and 2304 to these values.
• Resets 2305 to
OFF
.
Code Description
Speed reference
Actual speed
*
No acceleration compensation
Acceleration compensation
%
%
t
t
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...