LOW FREQ 1
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor stops if:
• Only one (the first) auxiliary motor is running.
• ACQ550 output frequency drops below the limit:
8112 - 1.
• Output frequency stays below the relaxed limit
(8112 + 1 Hz) for at least the time: 8116
AUX
MOT
STOP
D
.
After the first auxiliary motor stops:
• Output frequency increases by the value =
(8109
START
FREQ
1) - (8112
LOW
FREQ
1).
• In effect, the output of the speed regulated motor increases to
compensate for the loss of the auxiliary motor.
See the figure, where:
• A = (8109
START
FREQ
1) - (8112
LOW
FREQ
1)
• B = Output frequency decrease during the stop delay.
• C = Diagram showing auxiliary motor’s run status as frequency
decreases (1 = On).
• Grey path = Shows hysteresis – if time is reversed, the path
backwards is not the same. For details on the path for starting,
see the diagram at 8109
START
FREQ
1.
Note:
8112
LOW
FREQ
1 value must be between:
• (2007
MINIMUM
FREQ
) +1.
• 8109
START
FREQ
1
8113
LOW FREQ 2
Sets the frequency limit used to stop the second auxiliary motor.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
The second auxiliary motor stops if:
• Two auxiliary motors are running.
• ACQ550 output frequency drops below the limit: 8113 - 1.
• Output frequency stays below the relaxed limit (8113 + 1 Hz) for at least the time: 8116
AUX
MOT
STOP
D
.
8114
LOW FREQ 3
Sets the frequency limit used to stop the third auxiliary motor.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
The third auxiliary motor stops if:
• Three auxiliary motors are running.
• ACQ550 output frequency drops below the limit: 8114 - 1.
• Output frequency stays below the relaxed limit (8114 + 1 Hz) for at least the time: 8116
AUX
MOT
STOP
D
.
8115
AUX MOT START D
Sets the Start Delay for the auxiliary motors.
• The output frequency must remain above the start frequency limit (parameter 8109, 8110, or 8111) for this time
period before the auxiliary motor starts.
• See 8109
START
FREQ
1 for a complete description of the operation.
8116
AUX MOT STOP D
Sets the Stop Delay for the auxiliary motors.
• The output frequency must remain below the low frequency limit (parameter 8112, 8113, or 8114) for this time
period before the auxiliary motor stops.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
Code Description
t
t
f
(Hz)
f
MIN
f
MAX
P 8116
(P 8112)-1
B
1
0
C
P 8112
P 8109
A
A
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...