ACQ550-U1 User’s Manual
37
Start-up, control with I/O and ID Run
• Motor nominal current (parameter
)
Allowed range: 0.2…2.0 ·
I
2hd
A
• Motor nominal frequency (parameter
)
• Motor nominal speed (parameter
• Motor nominal power (parameter
Select the motor identification method (parameter
The default value 0 (
OFF
/
IDMAGN
) using the identification magnetization is suitable for most
applications. It is applied in this basic start-up procedure. Note however that this requires
that:
• parameter
is set to 1 or 2 (
VECTOR
:
SPEED
), or
• parameter
is set to 3 (
SCALAR
:
FREQ
) and parameter
is set to 3 (
SCALAR
FLYST
)
or 5 (
FLY
+
BOOST
).
If your selection is 0 (
OFF
/
IDMAGN
), move to the next step.
Value 1 (
ON
), which performs a separate ID Run, should be selected if:
• vector control mode is used [parameter
= 1 or 2 (
VECTOR
:
SPEED
)],
• the operation point is near zero speed, and/or
• operation at torque range above the motor nominal torque over a wide speed range and
without any measured speed feedback is required.
If you decide to do the ID Run [value 1 (
ON
)], continue by following the separate instructions
given on page
and then return to step
on page
.
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...