ACQ550-U1 User’s Manual
Embedded fieldbus
5303
EFB BAUD RATE
Defines the communication
speed of the RS485 link in
kbits per second (kbits/s).
1.2 kbits/s
2.4 kbits/s
4.8 kbits/s
9.6 kbits/s
19.2 kbits/s
38.4 kbits/s
57.6 kbits/s
76.8 kbits/s
When this protocol is
selected, the default
value for this
parameter is: 9.6
When this protocol is selected, the
default value for this parameter is:
38400
5304
EFB PARITY
Defines the data length, parity
and stop bits to be used with
the RS485 link communication.
• The same settings must be
used in all on-line stations.
0 = 8
N
1 – 8 data bits, No parity,
one stop bit.
1 = 8
N
2 – 8 data bits, No parity,
two stop bits.
2 = 8
E
1 – 8 data bits, Even
parity, one stop bit.
3 = 8
O
1 – 8 data bits, Odd
parity, one stop bit.
When this protocol is
selected, the default
value for this
parameter is: 1
When this protocol is selected, the
default value for this parameter is: 0
Do not edit.
5305
EFB CTRL PROFILE
Selects the communication
profile used by the EFB
protocol.
0 =
ABB
DRV
LIM
– Operation of
Control/Status Words
conform to ABB Drives
Profile (limited), as used in
ACQ550.
1 =
DCU
PROFILE
– Operation of
Control/Status Words
conform to 32-bit DCU
Profile.
2 =
ABB
DRV
FULL
– Operation
of Control/Status Words
conform to ABB Drives
Profile (full).
When this protocol is
selected, the default
value for this
parameter is: 0
N/A. When this protocol is selected,
the default value for this parameter
is: 0
Changing the value for this
parameter has no affect on this
protocol’s behavior.
5306
EFB OK MESSAGES
This parameter indicates the number of valid application
messages received at this drive. This count does not
include MS/TP token passing and polling messages. (For
such messages, see 5316).
5307
EFB CRC ERRORS
This parameter indicates the number of CRC errors
detected, in either the header or data CRCs.
5308
EFB UART ERRORS
This parameter indicates the number of UART-related errors
(framing, parity) detected.
Code
Description
EFB Protocol Reference
Modbus
BACnet
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...