150
ACQ550-U1 User’s Manual
4016
ACT1 INPUT
Defines the source for actual value 1 (
ACT
1). See also parameter 4018
ACT
1
MINIMUM
.
1 =
AI
1 – Uses analog input 1 for
ACT
1.
2 =
AI
2 – Uses analog input 2 for
ACT
1.
3 =
CURRENT
– Uses current for
ACT
1.
4 =
TORQUE
– Uses torque for
ACT
1.
5 =
POWER
– Uses power for
ACT
1.
6 =
COMM
ACT
1 – Uses value of signal 0158
PID
COMM
VALUE
1 for
ACT
1.
7 =
COMM
ACT
2 – Uses value of signal 0159
PID
COMM
VALUE
2 for
ACT
1.
4017
ACT2 INPUT
Defines the source for actual value 2 (
ACT
2). See also parameter 4020
ACT
2
MINIMUM
.
1 =
AI
1 – Uses analog input 1 for
ACT
2.
2 =
AI
2 – Uses analog input 2 for
ACT
2.
3 =
CURRENT
– Uses current for
ACT
2.
4 =
TORQUE
– Uses torque for
ACT
2.
5 =
POWER
– Uses power for
ACT
2.
6 =
COMM
ACT
1 – Uses value of signal 0158
PID
COMM
VALUE
1 for
ACT
2.
7 =
COMM
ACT
2 – Uses value of signal 0159
PID
COMM
VALUE
2 for
ACT
2.
4018
ACT1 MINIMUM
Sets the minimum value for
ACT
1.
• Scales the source signal used as the actual value
ACT
1 (defined
by parameter 4016
ACT
1
INPUT
). For parameter 4016 values
6 (
COMM
ACT
1) and 7 (
COMM
ACT
2) scaling is not done.
• See the figure: A= Normal; B = Inversion (
ACT
1
MINIMUM
>
ACT
1
MAXIMUM
)
4019
ACT1 MAXIMUM
Sets the maximum value for
ACT
1.
• See 4018
ACT
1
MINIMUM
.
4020
ACT2 MINIMUM
Sets the minimum value for
ACT
2.
• See 4018
ACT
1
MINIMUM
.
4021
ACT2 MAXIMUM
Sets the maximum value for
ACT
2.
• See 4018
ACT
1
MINIMUM
.
4022
SLEEP SELECTION
Defines the control for the PID sleep function.
0 =
NOT
SEL
– Disables the PID sleep control function.
1 =
DI
1 – Defines digital input
DI
1 as the control for the PID sleep function.
• Activating the digital input activates the sleep function.
• De-activating the digital input restores PID control.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for the PID sleep function.
• See
DI
1 above.
7 =
INTERNAL
– Defines the output rpm/frequency, process reference and process actual value as the control for the
PID sleep function. Refer to parameters 4025
WAKE
-
UP
DEV
and 4023
PID
SLEEP
LEVEL
.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for the PID sleep function.
• De-activating the digital input activates the sleep function.
• Activating the digital input restores PID control.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for the PID sleep function.
• See
DI
1(
INV
) above.
Code Description
Par 4016
Source
Source min.
Source max.
1
Analog input 1 1301
MINIMUM
AI
1
1302
MAXIMUM
AI
1
2
Analog input 2 1304
MINIMUM
AI
2
1305
MAXIMUM
AI
2
3
Current
0
2 · nominal current
4
Torque
-2 · nominal torque 2 · nominal torque
5
Power
-2 · nominal power 2 · nominal power
P 4019
P 4018
ACT
1 (%)
A
B
Source signal
Source min.
Source max.
P 4018
P 4019
ACT
1 (%)
Source signal
Source min.
Source max.
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...