ACQ550-U1 User’s Manual
75
Parameters
2906
RUN
TIME
ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
2907
USER
MWh
TRIG
0.0…6553.5 MWh, 0.0 disables
0.1 MWh
0.0 MWh
2908
USER
MWh
ACT
0.0…6553.5 MWh
0.1 MWh
0.0 MWh
Group 30: FAULT FUNCTIONS
3001
AI
<
MIN
FUNCTION
0…3
1
0 (
NOT
SEL
)
3002
PANEL
COMM
ERR
1…3
1
1 (
FAULT
)
3003
EXTERNAL
FAULT
1
-6…6
1
0 (
NOT
SEL
)
3004
EXTERNAL
FAULT
2
-6…6
1
0 (
NOT
SEL
)
3005
MOT
THERM
PROT
0 =
NOT
SEL
, 1 =
FAULT
, 2 =
ALARM
1
1 (
FAULT
)
3006
MOT
THERM
TIME
256…9999 s
1 s
500 s
3007
MOT
LOAD
CURVE
50…150%
1%
100%
3008
ZERO
SPEED
LOAD
25…150%
1%
70%
3009
BREAK
POINT
FREQ
1…250 Hz
1 Hz
35 Hz
3010
STALL
FUNCTION
0 =
NOT
SEL
, 1 =
FAULT
, 2 =
ALARM
1
0 (
NOT
SEL
)
3011
STALL
FREQUENCY
0.5…50.0 Hz
0.1 Hz
20.0 Hz
3012
STALL
TIME
10…400 s
1 s
20 s
3017
EARTH
FAULT
0
=
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3018
COMM
FAULT
FUNC
0 =
NOT
SEL
, 1 =
FAULT
, 2 =
CONST
SP
7,
3 =
LAST
SPEED
1
0 (
NOT
SEL
)
3019
COMM
FAULT
TIME
0.0…600.0 s
0.1 s
3.0 s
3021
AI
1
FAULT
LIMIT
0.0…100.0%
0.1%
0.0%
3022
AI
2
FAULT
LIMIT
0.0…100.0%
0.1%
0.0%
3023
WIRING
FAULT
0 =
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3024
CB
TEMP
FAULT
0 =
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3028
EARTH
FAULT
LVL
1 =
LOW
, 2 =
MEDIUM
, 3 =
HIGH
1
1 (
LOW
)
Group 31: AUTOMATIC RESET
3101
NUMBER
OF
TRIALS
0…5
1
5
3102
TRIAL
TIME
1.0…600.0 s
0.1 s
30.0 s
3103
DELAY
TIME
0.0…120.0 s
0.1 s
6.0 s
3104
AR
OVERCURRENT
0 =
DISABLE
, 1 =
ENABLE
1
0 (
DISABLE
)
3105
AR
OVERVOLTAGE
0 =
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3106
AR
UNDERVOLTAGE
0 =
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3107
AR
AI
<
MIN
0 =
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3108
AR
EXTERNAL
FLT
0 =
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
Group 32: SUPERVISION
3201
SUPERV
1
PARAM
100 =
NOT
SELECTED
, 101…178
1
102 (parameter 0102
OUTPUT
SPEED
)
3202
SUPERV
1
LIM
LO
-
-
Depends on the signal
selected with par. 3201
3203
SUPERV
1
LIM
HI
-
-
Depends on the signal
selected with par. 3201
3204
SUPERV
2
PARAM
100 =
NOT
SELECTED
, 101…178
1
104 (parameter 0104
CURRENT
)
3205
SUPERV
2
LIM
LO
-
-
Depends on the signal
selected with par. 3204
3206
SUPERV
2
LIM
HI
-
-
Depends on the signal
selected with par. 3204
Code
Name
Range
Resolution
Default
User
S
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...