ACQ550-U1 User’s Manual
159
Group 53: EFB PROTOCOL
This group defines set-up variables used for an embedded fieldbus (EFB)
communication protocol. The standard EFB protocol in the ACQ550 is Modbus. See
chapter
page
Code Description
5301
EFB PROTOCOL ID
Contains the identification and program revision of the protocol.
• Format: XXYY, where xx = protocol ID, and YY = program revision.
5302
EFB STATION ID
Defines the node address of the RS485 link.
• The node address on each unit must be unique.
5303
EFB BAUD RATE
Defines the communication speed of the RS485 link in kbits per second (kb/s).
1.2 kb/s
2.4 kb/s
4.8 kb/s
9.6 kb/s
19.2 kb/s
38.4 kb/s
57.6 kb/s
76.8 kb/s
5304
EFB PARITY
Defines the data length, parity and stop bits to be used with the RS485 link communication.
• The same settings must be used in all on-line stations.
0 = 8
NONE
1 – 8 data bits, no parity, one stop bit.
1 = 8
NONE
2 – 8 data bits, no parity, two stop bits.
2 = 8
EVEN
1 – 8 data bits, even parity, one stop bit.
3 = 8
ODD
1 – 8 data bits, odd parity, one stop bit.
5305
EFB CTRL PROFILE
Selects the communication profile used by the EFB protocol.
0 =
ABB
DRV
LIM
– Operation of Control/Status Words conforms to ABB Drives Profile, as used in ACS400.
1 =
DCU
PROFILE
– Operation of Control/Status Words conforms to 32-bit DCU Profile.
2 =
ABB
DRV
FULL
– Operation of Control/Status Words conforms to ABB Drives Profile, as used in ACS600/800.
5306
EFB OK MESSAGES
Contains a count of valid messages received by the drive.
• During normal operation, this counter is increasing constantly.
5307
EFB CRC ERRORS
Contains a count of the messages with a CRC error received by the drive. For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels generate errors.
• CRC calculations for possible errors.
5308
EFB UART ERRORS
Contains a count of the messages with a character error received by the drive.
5309
EFB STATUS
Contains the status of the EFB protocol.
0 =
IDLE
– EFB protocol is configured, but not receiving any messages.
1 =
EXECUT
INIT
– EFB protocol is initializing.
2 =
TIME
OUT
– A timeout has occurred in the communication between the network master and the EFB protocol.
3 =
CONFIG
ERROR
– EFB protocol has a configuration error.
4 =
OFF
-
LINE
– EFB protocol is receiving messages that are NOT addressed to this drive.
5 =
ON
-
LINE
– EFB protocol is receiving messages that are addressed to this drive.
6 =
RESET
– EFB protocol is performing a hardware reset.
7 =
LISTEN
ONLY
– EFB protocol is in listen-only mode.
5310
EFB PAR 10
Specifies the parameter mapped to Modbus Register 40005.
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...