ACQ550-U1 User’s Manual
255
Diagnostics
28
SERIAL
1
ERR
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
).
• Communication settings (
as appropriate).
• Poor connections and/or noise on line.
29
EFB
CON
FILE
Error in reading the configuration file for the embedded fieldbus.
30
FORCE
TRIP
Fault trip forced by the fieldbus. See the fieldbus User’s Manual.
31
EFB
1
Fault code reserved for the embedded fieldbus (EFB) protocol application.
The meaning is protocol dependent.
32
EFB
2
33
EFB
3
34
MOTOR
PHASE
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
35
OUTP
WIRING
Possible power wiring error detected. When the drive is not running it
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltage is NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
WIRING
FAULT
.
36
INCOMPATIBLE
SW
The drive cannot use the software.
• Internal fault.
• The loaded software is not compatible with the drive.
• Call support representative.
37
CB
OVERTEMP
Drive control board is overheated. The fault trip limit is 88 °C. Check for and
correct:
• Excessive ambient temperature.
• Fan failure.
• Obstructions in the air flow.
38
USER
LOAD
CURVE
Condition defined by parameter 3701
USER
LOAD
C
MODE
has been valid
longer than the time defined by 3703
USER
LOAD
C
TIME
.
101…
199
SYSTEM
ERROR
Error internal to the drive. Contact your local ABB representative and report
the error number.
201…
299
SYSTEM
ERROR
Error in the system. Contact your local ABB representative and report the
error number.
-
UNKNOWN
DRIVE
TYPE
:
ACQ550
SUPPORTED
DRIVES
:
X
Wrong type of panel, i.e. panel that supports drive X but not the ACQ550,
has been connected to the ACQ550.
Fault
code
Fault name in
panel
Description and recommended corrective action
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...