Customer parameters

v/f operation

Translation of original manual

Document

Part

version

Date

20096630

GBR

00

1214

Summary of Contents for COMBIVERT G6

Page 1: ...U f UN fN C O M B I V E R T Customer parameters v f operation Translation of original manual Document Part version Date 20096630 GBR 00 1214...

Page 2: ......

Page 3: ...ty 4 1 4 Copyright 5 1 5 Specified application 6 1 6 Product description 6 1 6 1 Corresponding documentation 6 2 Parameter Description 7 2 1 Selection of the customer parameter menu 7 2 2 Password inp...

Page 4: ...with the unit the user must become familiar with it This includes especially the knowledge and observance of the safety and operating instructions Attention Observe safety and operating instructions P...

Page 5: ...ecome void invalid or impracticable the effectivity of all other regulations or agreements is not affected Through multitude applications not each possible case of installation operation or mainte nan...

Page 6: ...hines which work under exceptional conditions or if essential functions life supporting measures or an extraordinary safety step must be fulfilled the necessary reliability and secu rity must be ensur...

Page 7: ...this manual is valid for open loop systems That can be indentified by parameter CP48 see below 2 1 Selection of the customer parameter menu CP48 Software version Co domain Setting Description 0 0 0 0...

Page 8: ...atz 0 Passwort 1 Passwort CP Mode Schreibschutz Men Oben Unten CP00 Passwort 0 CP Mode Schreibschutz CP01 Istwertanzeige 0 50 0000 Hz CP02 Sollwertanzeige 0 50 0000 Hz CP03 Umrichterstatus 0 Konstantf...

Page 9: ...17 Voltage stabilization 0 649 1 off V E uF09 CP18 Switching frequency 0 LTK 1 LTK E uF11 CP19 step value 1 400 400 0 0125 5 Hz oP21 CP20 step value 2 400 400 0 0125 50 Hz oP22 CP21 step value 3 400 4...

Page 10: ...ayed in parameter inverter state In the case of an error the current error message is dis played even if the display has already been reset with ENTER status LED is still blinking Display State no ope...

Page 11: ...the address of CP05 The switch off of the inverter also clears the memory CP06 DC link voltage peak value Co domain Description 0 400 Display of the actual inverter rate of utilization in percent 100...

Page 12: ...ss of CP08 The switch off of the inverter also clears the memory CP09 Output voltage Co domain Description 0 778V Display of the actual output voltage in volt CP10 min reference forward Co domain Sett...

Page 13: ...s the time needed to accelerate from 0Hz to100Hz or to decelerate from 100Hz to 0Hz The actual acceleration deceleration time is proportion al to the frequency change f f Frequency change t s CP12 f H...

Page 14: ...vated S curve time the preset acceleration and deceleration times CP12 and CP13 must be ad justed higher than the S curve time CP14 CP15 Boost Co domain Setting Description 0 0 25 5 LTK In the lower s...

Page 15: ...lization Co domain Setting Description 1 650V off 650V off With this parameter a regulated output voltage in relation to the rated frequency can be adjusted For that reason voltage variations at the i...

Page 16: ...echnical data of the power circuit manual CP19 Step value 1 CP20 Step value 2 CP21 Step value 3 Co domain Setting Description CP19 0 400Hz 5Hz Three fixed frequencies can be adjusted The selection is...

Page 17: ...ontrol release 32 DC braking after switching on 64 DC braking after reset 128 DC braking after auto reset 256 DC braking after LS 11 15 reserved Braking time depends on the actual frequency CP23 DC br...

Page 18: ...elease 2 at switch on 4 after reset 8 after Auto Reset UP 16 after LS CP27 Motor protect function response The warning function protects the connected motor against thermal destruction caused by high...

Page 19: ...ck stopping holding torque automatic restart Status message Warning Fast stop holding torque on reaching 0Hz the drive returns automatically to normal operation as soon as the fault no longer exists 6...

Page 20: ...vel for transistor output 1 is preset to 4 00 CP33 Condition SB2 The switching level for relay output 1 is adjusted with CP34 setting 100 00 Value Function 0 No function generally off 1 Generally on 2...

Page 21: ...2 warning 52 Current regulator limit reached 59 Inputs in AND operation ru22 60 Inputs in OR operation ru22 61 Inputs in NAND operation ru22 62 Inputs in NOR operation ru22 63 Absolute ANOUT1 switchin...

Page 22: ...an adaption of the factory setting to the valid operating data there can be done with this parameter The control release must be opened for the changeover since otherwise error Operation not possible...

Page 23: ...function is only triggered when the inverter modu lates Remove fault reset 9 As value 6 additionally the motor monitoring is also active when the modulation is switched off 1 ERROR drive overheat 2 AB...

Page 24: ...cust sys sel sets Default values are copied in all parameters of the target set exception security parameters If the target set is 0 only programmable parameters are copied 4 KEBdef cust sys all sets...

Page 25: ...ndition of the unit They have no special identifi cation and are used for information only Error messages always consist of the word Error and the cause Error messages cause the immediate deactivation...

Page 26: ...e is stopped no ABN STOP overload 98 Warning no more overload OL counter has reached 0 warning overload can be reset no ABN STOP overload 2 101 The cooling time after Warning Overload during stand sti...

Page 27: ...stall 71 This message is displayed if during constant operation the load is limited to the adjusted current limit no ERROR overload 17 No more overload OL counter has reached 0 after Error overload a...

Page 28: ...58 The speed is outside the defined limits can also occur on exceeding of the absolute speed referring to EMF EMF wrong servo drives ERROR overheat internal 6 Overheating in the interior Error can onl...

Page 29: ...rload in the application inverter not correctly dimensioned motor wrongly wired poor controller adjustment ERROR overload 2 19 Occurs if the current for zero speed is exceeded see technical data in th...

Page 30: ...l fault 90 This warning is triggered via an external input The res ponse to this warning can be programmed ABN STOP motor protect 97 Warning electronic motor protective relay has tripped The response...

Page 31: ...n the defined level is exceed ed Furthermore the response to this warning can be programmed ABN STOP bus 93 Watchdog for the communication between control board and PC on an optional fieldbus interfac...