9.14.2
Manual addressing
•
The members are connected to the device by the terminals 1A(1D+) and 1B (1D-) (see Installation /
RS-485 interfaces for MODBUS RTU).
•
All bus members to be addressed must be connected with one other in order for manual addressing
to be successful.
•
Only connect the bus members currently to be addressed to the voltage and switch on, not all the
other members during the addressing operation.
Main menu
MODBUS Master
"
Press the P-key
to open the
“
MODBUS Master
”
.
Limits
Timer
Diagnostic
MODBUS Master
[P] Enter
[ESC] Info
MODBUS Master
Auto Address
[P] Enter
[ESC] Menu
MODBUS Master
"
Press the
▼
key
to select the
“
ManualAddressing
”
menu.
"
Press the P-key
to open the menu.
Manual address
[P] Edit
[ESC] Menu
MODBUS Master
"
Set the lowest desired address using the
▼
+
▲
keys and con
fi
rm with the
P
key
.
4
Select address
[P] Start
[ESC] Menu
Manual address
"
Select the type with the
▼
+
▲
keys and con
fi
rm with the
P key
.
–
ZA ECblue
–
ZA B-G-028NE
ZA ECblue
Select type
[P] OK
[ESC] Cancel
Manual address
"
Connect device to voltage and switch on
"
Press the P key
to perform addressing.
Switch on device
4
[P] OK
[ESC] Cancel
Manual address
"
Set the desired address with the
▼
+
▲
keys (higher than addresses already
assigned).
"
Press the P key
to perform addressing of more members.
5
Select address
[P] Next
Manual address
Error message for unsuccessful addressing.
Addressing Error
[P] Next
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
96/121