Base setup
E1 Setpoint min
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: minimum measurement value
0 m
3
/h
E1 Setpoint min
Base setup
E1 Setpoint max
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: maximum measurement value
1060 m
3
/h
E1 Setpoint max
Base setup
E2 Function
The second signal input is not activated at the factory for modes with one sensor.
The function is automatically jointly programmed in operating modes using 2 sensors.
The second analog input is thus allocated and additional function allocations are not
possible.
Modes with two sensors
•
For
5.02
E2 Function at
|
6E
|
preprogrammed = sensor for setpoint lowering.
Preprogrammed sensor type
“
TF..
”
Adjustable
“
E2 function
”
for modes with one sensor
•
|
1E
|
= external setpoint e.g. by external signal (0 - 10 V) instead of setting
“
Setpoint 1
”
. 0 - 10 V
0 - 100 % setting range.
•
|
2E
|
= External manual operation via external signal (0 - 10 V). Switch over
between settings on the device and external manual operation via digital input (
IO Setup: function
|
7D
|
).
•
|
3E
|
= Sensor average to E1
•
|
4E
|
= Sensor comparison to E1
•
|
5E
|
= Sensor difference to E1
•
|
7E
|
= Measurement value = Measurement value e.g. for limit indication, display in
Info menu
“
E2 Actual
”
.
•
|
8E
|
...
|
13E
|
= sensor input for control circuit 2 see Base setup / operation
with second control circuit.
OFF
E2 Function
K-Factors for ZIEHL-ABEGG fans
Size
C-series
Cpro-series
Vpro-series
M-series
ZAvblue
Impeller diameter
[mm]
K-Factor [SI-units]
K-Factor [SI-units]
K-Factor [SI-units]
K-Factor [SI-units]
225
47
57
250
60
68
280
75
86
86
95
315
95
112
96
120
355
121
144
142
150
400
154
180
172
200
450
197
220
217
240
500
252
291
274
320
560
308
360
400
630
381
445
480
710
490
800
620
900
789
1000
999