9.10.6.5
Output control circuit 2 additional to
“
A2
”
on
“
A1
”
, function
|
4D
|
The output for control circuit 2 is set additionally to
“
A2
”
to
“
A1
”
(regardless of the programmed function
for
|
A1
|
). Control circuit 1 has no output for the duration of the switching.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
At
“
D1
”
Inverting
“
OFF
”
the output of control circuit 2 also in
fl
uences output
“
A1
”
when the contact is
closed.
1
0
n = 0 - 100 %
03.04.2013
v_4d_contr2_a2_or_plus_a1.vsd
0
1
Controller 1
n = 0 - 100 %
A1
A2
D1
24V
D1
Sensor 1
Controller 2
Sensor 2
9.10.6.6
Set 1/2 or Setpoint 1/2, Function
|
5D
|
For Mode Speed controller
1.01
: Switch over
“
Set Intern1
”
/
“
Set Intern2
”
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Controller
24V
D1 D1
1
0
n = 40 %
1
n = 80 %
0
- - - - -
- - - - -
11.05.2007
v_5d_vorgabe_intern_1_2.vsd
2
1
1
Setting
“
Set Intern1
”
(depending on device type in: %, Hz, rpm)
2
Setting
“
Set Intern2
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Set Intern1
”
at
opened contact /
“
Set Intern2
”
at closed
contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
Set Intern1
”
at
closed contact /
“
Set Intern2
”
at opened
contact.
Info
Operation with
“
Set Intern2
”
is signalized by the moon symbol for reduced operation.
“
Set extern1
”
under
“
settings
”
must be programmed to
“
OFF
”
.
50 %
Modulation
For operation as controller (starting from
2.01
): switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
For operation with second control circuit: switch over
“
1.Setpoint 1
”
/
“
1.Setpoint 2
”
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Controller
1
0
n = 0 – 100 %
- - - - -
- - - - -
Sensor
11.05.2007
v_5d_sollwert_1_2.vsd
2
1
24V
D1 D1
1
Setting
“
Setpoint 1
”
or
“
1.Setpoint 1
”
(display in operation with two
control circuits for Setpoint 1 of control circuit 1)
2
Setting
“
Setpoint 2
”
or
“
1.Setpoint 2
”
(display in operation with two
control circuits for Setpoint 2 of control circuit 1)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Setpoint1
”
=
18
°
C at opened contact /
“
Setpoint2
”
=
25
°
C at closed contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
Setpoint1
”
= 18
°
C
at closed contact /
“
Setpoint2
”
= 25
°
C at
opened contact.
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001