9.14.1
Automatic addressing
•
The
fi
rst member (MODBUS address
1
) must be connected to the terminals 1A(1D+) and 1B (1D-),
additionally the
“
ID
”
connections must be connected (see Installation / Communication / Addressing
members MODBUS Master interface).
•
The members are automatically addressed consecutively according to the installation.
•
In order to do the automatic addressing successfully, all the bus members to be addressed must be
connected with each other, applied to voltage and switched on.
Information
The automatic addressing can only be done with compatible devices!
Main menu
MODBUS Master
1.
Press the P-key
to open the
“
MODBUS Master
”
.
Limits
Timer
Diagnostic
MODBUS Master
[P] Enter
[ESC] Info
MODBUS Master
1.
Press the P-key
to select automatic addressing.
2.
Press the P-key
to start automatic addressing.
Auto Address
[P] Enter
[ESC] Menu
MODBUS Master
Display while the automatic addressing is in progress.
Addressing
Found: 0
In progress
[P] Repeat
[ESC] Cancel
MODBUS Master
The found members count is displayed at the end of automatic addressing.
Press the
P-key
again to repeat the addressing.
Exit the menu with [ESC].
Addressing
Found: 5
Done
[P] Repeat
[ESC] Cancel