1
0
n = 0 - 100 %
04.04.2013
v_15d_umsch_sollw_plus_regelb_kreis1.vsd
Controller 1
n = 0 - 100 %
A1
A2
D1
24V
D1
Sensor 2
Controller 2
Sensor 1
15D
1.Setpoint1
Setting
“
1.Setpoint 1
”
= Setpoint 1 of control circuit 1
1.Pband1
Setting
“
1.Pband 1
”
= Pband 1 von control circuit 1
1.Setpoint2
Setting
“
1.Setpoint 2
”
= Setpoint 2 of control circuit 1
1.Pband2
Setting
“
1.Pband 2
”
= Pband 1 von control circuit 1
Info
Operation with
“
1.Setpoint2
”
and
“
1.Pband2
”
is signalized by the moon symbol for
reduced operation.
If Setpoint 2 was activated additionally for control circuit 1 or control circuit 2 by a digital
input with function
|
5D
|
/
|
9D
|
the moon symbol is already switched on.
If Setpoint 2 and Pband 2 were activated additionally for control circuit 2 by a digital
input with function
|
16D
|
, the moon symbol is already switched on.
28.7
°
C
E1 Actual
9.10.6.14
Switch over Setpoint 1/2 and Pband 1/2 for control circuit 2
|
16D
|
Switch over between
“
2.Setpoint 1
”
/
“
2.Setpoint 2
”
and
“
2.Pband 1
”
/
“
2.Pband 2
”
(only for operation
with second control circuit possible).
Function basically the same as
|
5D
|
and
|
9D
|
,it is additionally switched over to Pband 2.
When programming this function,
“
Setting
”
additionally lists the parameter:
“
2.Pband 2 for control
circuit 2
”
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Example for
“
D1 Inverting
”
=
“
OFF
”
:
•
With open contact:
“
2.Setpoint 1
”
= 20
°
C +
“
2.Pband 1
”
= 5 K
•
With closed contact:
“
2.Setpoint 2
”
= 17
°
C +
“
2.Pband 2
”
= 3 K
1
0
n = 0 - 100 %
04.04.2013
v_16d_umsch_sollw_plus_regelb_kreis2.vsd
Controller 2
n = 0 - 100 %
A2
A1
D1
24V
D1
Sensor 2
Controller 1
Sensor 1
16D
2.Setpoint1
Setting
“
2.Setpoint 1
”
= Setpoint 1 of control circuit 2
2.Pband1
Setting
“
2.Pband 2
”
= Pband 1 von control circuit 2
2.Setpoint2
Setting
“
2.Setpoint 2
”
= Setpoint 2 control circuit 2
2.Pband2
Setting
“
2.Pband 2
”
= Pband 2 von control circuit 2
Info
Operation with
“
2.Setpoint2
”
and
“
2.Pband2
”
is signalized by the moon symbol for
reduced operation.
If Setpoint 2 was activated additionally for control circuit 1 or control circuit 2 by a digital
input with function
|
5D
|
/
|
9D
|
the moon symbol is already switched on.
If Setpoint 2 and Pband 2 was activated additionally for control circuit 1 by a digital
input with function
|
15D
|
, the moon symbol is already switched on.
28.7
°
C
E2 Actual
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
83/121