13.03.2015
v_cxe_comparator_c1_c2.vsd
Controller 1
A2
Sensor 1
Controller 2
Sensor 2
C2
C1
Comparator
Cout = C1 @ C1 > C2
Cout = C2 @ C2 > C1
Cout
A1
9.9.13
COM2 Function
IO Setup
Possible settings:
•
MODBUS Slave (factory setting): In the main menu the
“
Diagnostic
”
menu group is
followed by the
“
MODBUS Slave
”
menu group. The communication parameters
can be set in this.
•
OFF: The
“
MODBUS Slave
”
or
“
MODEM SMS
”
menu group is not displayed in
the main menu.
•
MODEM SMS: In the main menu the
“
IO Setup
”
menu group is followed by the
“
MODEM SMS
”
menu group. Input
SIM
PIN for MODEM
SMS
interface (no
function at present).
MODBUS Slave
COM2 Function
9.9.14
Data on the total control deviation
The total control deviation is comprised of the sum of the control deviations for performance quantities
and work quantities combined and refers to the speci
fi
ed areas.
In direct reference to the acquired input and controlled variables, the maximum deviation to the target
value is <
±
5 %. By activating the menu-assisted adjustment, the total control deviation can be
reduced to a value of <
±
1 %.
For indirect reference of the acquired input value to the controlled variable, i.e., two physical variables
still need to be converted, the deviation can be reduced to <
±
5 % through adjustment.
In the case of an internal default value through the integrated or external terminal, the control deviation
remains at <
±
0.5%.
9.10
IO Setup
9.10.1
overview Menu group IO Setup
Main menu
IO Setup
Settings
Protocol
Base setup
Controller Setup
IO Setup
IO Setup
The IO setup consists of 4 areas:
Analog Out
Analog outputs
Analog In
Analog inputs
Digital Out
Digital outputs
Digital In
Digital inputs
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
63/121