Info
Operation with
“
Setpoint2
”
is signalized by the moon symbol for reduced operation.
28.7
°
C
E1 Actual
9.10.6.7
Intern / Extern Function
|
6D
|
For Mode Speed controller
1.01
: Switch over
“
Set Intern
”
/
“
Set external
”
“
Set extern1
”
under settings must be programmed to
“
OFF
”
.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Controller
24V
D1 D1
1
0
n = 40 %
n = 80 %
Si 40 %
- - - - -
E1
11.05.2007
v_6d_vorgabe_intern_extern.vsd
1
0
1
Si
Signal
1
Setting
“
Set Intern1
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Set Intern1
”
at
opened contact /
“
Setting Extern
”
at closed
contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
Set Intern1
”
at
closed contact /
“
Set Extern
”
at opened
contact.
For operation as controller (starting from
2.01
): switch over
“
Setpoint 1
”
/
“
external Setpoint
”
Possible only for operation with one control circuit!
Under Base setup
“
E2 function
”
programmed to function
|
1E
|
for
“
external setpoint
”
.
Contact at digital input e.g.
“
Digital In 1
”
=
“
D1
”
-
“
D1
”
Controller
24V
D1 D1
1
0
n = 0 – 100 %
- - - - -
Se
ES
E2
26.05.2010
v_6d_sollwert1_externer_sollwert.vsd
1
1
Setting
“
Setpoint1
”
ES
External Setpoint e.g. 5 V
23.8
°
C
Se
Sensor
•
“
D1 Inverting
”
=
“
ON
”
: Setting at the unit at
opened contact / Signal Extern at closed
contact
•
“
D1 Inverting
”
=
“
OFF
”
: Setting at the unit
at closed contact / Signal Extern at opened
contact
9.10.6.8
Automatic control / speed manual Function
|
7D
|
(mode
2.01
)
Possible only for operation with one control circuit!
Switch over between automatic control to set target value (depending on the activation:
“
Setpoint1
”
,
“
Setpoint2
”
) and the default for
“
manual operation
”
set at the device.
If for Analog In 2
“
E2 function
”
is programmed to
|
2E
|
switch over between
“
Setpoint1
”
or
“
Setpoint2
”
and external manual operation. With activated manual mode the display constantly changes between
“
actual value
”
and value for
“
manual mode
”
.
Contact at digital input e.g.
“
Digital In 1
”
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.