9.10.6
Digital inputs
“
DI
”
Menu overview
Digital In
DI1 (OFF)
DI2 (OFF)
DI3 (OFF)
DI4 (OFF)
DI5 (OFF)
▲
▼
Overview of possible digital in-
puts
P
↓
↑
ESC
DI1
OFF
Function
P
▲
▼
Setting of the desired function
▲
▼
DI1
D1
Signal
P
▲
▼
Assignment: Virtual input / ac-
tual input
▲
▼
DI1
OFF
Invertierung
P
▲
▼
Inverting input
Overview of possible digital inputs
Digital In
Example to explain the display
DI1 (0, 1D)
0 = Input DI1 not active
1D = Programmed function (enable) for
“
DI1
”
DI2 (1, 3D)
1 = input DI2 active
3D = Programmed function (limit) for
“
DI1
”
DI3 (OFF)
OFF = No function assigned
DI4 (OFF)
OFF = No function assigned
DI5 (OFF)
OFF = No function assigned
DI6 (OFF)
OFF = No function assigned
Setting of the desired function
Function
Designation
OFF
no function (factory setting)
Enable
(1D)
Enable (remote control)
“
ON
”
/
“
OFF
”
External error
(2D)
External fault alarm
Limit
(3D)
“
Limit
”
ON / OFF
In
fl
uences control circuit 1 and control circuit 2 in operation with two control circuits
E1 / E2
(4D)
Switch over input
“
E1
”
/
“
E2
”
(for operation with one control circuit)
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
75/121