MODBUS Slave
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Factory setting: 8E1
8E1
UART Mode
9.14
MODBUS Master
Addressing of the members that are activated via the MODBUS Master interface.
Addressing can be done automatically by a patented method. It is then no longer necessary to
address every single member manually in the network.
Alternatively, manual addressing with free assignment of the address is possible (see Manual
addressing).
Information
•
A
maximum of 32 devices
can be connected. The communication settings are pre-set to 19.2kbd,
8E1 and cannot be changed.
•
To ensure activation, the function of the digital input
“
D1
”
of the members is automatically set to
“
OFF
”
by the MODBUS Master. I.e. any programmed enable function for switching off the member
(by a potential-free contact) is no longer active.
Main menu
MODBUS Master
After addressing (manual or automatic), the devices are subsequently listed to the
“
MODBUS Master
”
menu group (see
“
Members MODBUS Master
”
).
MODBUS Master
Fan 1 (2A)
Fan 2 (2A)
Fan 3 (2A)
[P] Enter
[ESC] Info
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
94/121