4.2
Prerequisites for mounting
Type CXE/AV & CXG-24AV (version for wall mounting)
•
The device is designed for vertical installation (bottom cable inlet). A horizontal or reclined installa-
tion is only permissible after technical release of the manufacturer!
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use the
appropriate mounting devices for proper installation of the unit!
Proceed as follows:
1. Remove the terminal compartment cover.
2. Create mounting holes (dimension sheet see enclosure).
3. Screw in the two upper
fl
ad head screws up to a distanse of approx. 2 mm and hang on the
device.
4. Screw in the two lower
fl
ad head screws (tightening torque 2 Nm).
5. Insert cables properly and ensure tightness of the cable inlet.
6. Unused entry points must be sealed!
7. Attach the cover of terminal compartment again carefully after connection (see Electrical Installa-
tion).
Type CXE/AVE & CXG-24AVE (version for panel mounting)
•
The device ist desiged for installation in a front panel. The installation position is horizontal.
•
Necessary panel cut-out: 174.5 mm x 110.5 mm (Dimension sheet see Enclosure).
•
Permissible panel thickness: 1 - 4 mm.
Proceed as follows:
1. Insert the device from the front in the cut opening.
2. Attach side
fi
xing brackets from the rear to the device and tighten the enclosed screws uniformly
(tightening torque 0.5 Nm).
Operating Instructions
UNIcon MODBUS Master
Mounting
L-BAL-E255-GB 1901 Index 001
Part.-No.
9/121