
9.1.2
Speed controller with direct setting by keyboard
1.02
Base setup
1.02
Main menu
Base setup
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
Mode
Mode selection:
1.02
1.02
Mode
Base setup
Number steps
Selection: 0, 1, 2, 3, 4, 5
Factory setting:
0
Number steps: 0
In the factory setting
“
0
”
(without steps) the output frequency can be set directly with
the
▼
+
▲
keys (see setting in operation).
Number steps: 1, 2, 3, 4, 5
The modulation value can be assigned to each step. The desired step is set with the
▼
▲
keys (see setting in operation).
The following menus become active depending on the selected step count. (Step not
active =
|
- - - -
|
)
0
Number steps
Base setup
Step 1 value - 5
Setting range: 0...100 %.
Factory setting: - - - - - (Number steps 0)
Factory setting: 20 %, 40 %, 50 %, 60 %, 100 % (Number steps 1 - 5)
- - - - -
Step 1 value
Menu group
“
setting
”
(only when needed)
Main menu
Setting
Setting
Protocol
Base setup
Controller Setup
IO Setup
Setting
Setting direct
(at Number steps: 0 see
“
Base setup
”
)
If the setting is to be made during operation directly with the
▼
▲
keys, no setting is
necessary here (see setting in operation
1.02
).
Setting range: Min. Speed - Max. Speed
Factory setting: 80 %
80 %
Setting direct
Setting
Setting step
(at Number steps: 1 - 5 see
“
Base setup
”
)
If the setting is to be made during operation directly with the
▼
▲
keys, no setting is
necessary here (see setting in operation
1.02
).
Setting range: 0 - setting nummber steps
Factory setting: 0
0
Setting Step
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
29/121