Controller Setup
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
20 %
nmin at Group2
Controller Setup
Group 3 ON value
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 70 % *
70 %
Group 3 ON value
Controller Setup
OFF Value Group3
Switch-off value for group3
Setting range: 0 - 100 %
Factory setting: 65 *
65 %
OFF Value Group3
Controller Setup
nmin at Group3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 30 % *
30 %
nmin at Group
3
Controller Setup
Group 4 ON value
Switch-on value for Group4
Setting range: 0 - 100 %
Factory setting: 85 % *
85 %
Group 4 ON value
Controller Setup
OFF Value Group4
Switch-off value for group4
Setting range: 0 - 100 %
Factory setting: 80 % *
80 %
OFF Value Group4
Controller Setup
nmin at Group4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 40 % *
40 %
nmin at Group4
*
Display as long as no group assignment via analogue output, relay, MODBUS:
|
- - - -
|
Higher settings must be selected for following groups and the switch-off value of the group must be
below the switch-on value.
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
60/121