Setting
Set Internal2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over setpoint 1/2 over external contact (display where no allocation:
|
- - - - -
|
see IO Setup).
- - - - -
Set Internal2
Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Passive sensor type
“
TF
”
,
“
PT1000
”
Setting range: 0 - 200.0 K (Kelvin)
Factory setting: 5.0 K, (at
2.02
: 20.0 K)
active Sensor type
“
MTG-120V
”
Setting range: -10.0...+120.0 K
Factory setting: 65.0 K
5.0 K
Pband
Setting
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Setting
Max. Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (see IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
33/121