Operating h group4
12
Protocol
12.1
Display and query of events and malfunctions
Main menu
Events during operation can lead to a malfunctioning of the device.
The last 100 events are saved in the
“
Protocol
”
menu group.
Position 1 = latest event, display: Protocol 1/100
Position 100 = last saved event, display: Protocol 100/100
The saved events are retained even after resetting to factory setting (
menu
group Start / PIN input)!
Start up
Setting
Protocol
Base setup
Controller Setup
The device distinguishes between several event types which are identi
fi
ed by different symbols.
Examples
Protocol 1/100
Attention symbol = message
Modulation
Runtime Controller
000493:04:59
The message is only listed in the protocol. There is no message alternately with
the actual value display and no message via alarm relay.
Exception
In case of sensor failure there is always a message in the display (
Controller
Setup / Alarm Sensors) .
Protocol 2/100
Bell symbol = Alarm
Error MODBUS Com
Runtime Controller
000193:04:59
The alarm message is listed in the protocol and appears alternately with the
actual value display.
Message by alarm relay depending on the type of failure and programming.
Protocol 2/100
Cross symbol = previous messages
Line Fault
Runtime Controller
000493:04:59
Cause of the message no longer exists.
Operating Instructions
UNIcon MODBUS Master
Protocol
L-BAL-E255-GB 1901 Index 001
Part.-No.