Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 100 Pa
100 Pa
Pband
Setting
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Setting
Max. Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (see IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
Additional menu item for mode
4.02
and
4.03
with outside-temperature dependent target-
setpoint.
Outside-temperature dependent target-setpoint
AT
P-min.
-15 °C
T-min.
30 °C
T-Start
S1
18.09.2014
v_pressure_set_dep_outtemp.vsd
[Pa]
S2
T-Band
S1
Setpoint1
S2
Set Internal2
P-min.
Min. Setpoint
T-min
Min. temperature
T-Start
Setpoint reducing will start below this outside temperature
T-band
Temperature range
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
=
“
Analog In
2
”
) when being operated as a pressure regula-
tion device.
Through this function, the set and active
“
Set-
point 1
”
or
“
Setpoint 2
”
is automatically changed
proportional to the measured outside tempera-
ture (see Info:
“
Setpoint control
”
).
Setting
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
Setting range: 0.0..100.0 K
Factory setting: 30.0 K
30 K
T-Band SA
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
44/121