Only active in operation with a second control circuit
E1 / E2
(4D)
The output for control circuit 2 is set additionally to
“
A2
”
to
“
A1
”
(regardless of the
programmed function for
|
A1
|
). The
fi
rst control circuit has no output for the duration of
the switch over.
The switch over input
“
E1
”
/
“
E2
”
as in operation with one control circuit is no longer
possible.
2. Setpoint 1/2
(9D)
for control circuit 2: Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
2.Setp+Pband1/2
(16D)
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function,
“
Setting
”
additionally lists the parameter:
“
2.Pband 2
for control circuit 2
”
Functions 12D, 13D and 22D to 29 D without function!
Limits GW E1 and GW E2
Function
Description function GW E1, GW E2
OFF
no function
Fault
(1L)
Indication with the centralized fault of a programmed relay (IO allocation Function
|
2K
|
).
Warning symbol in display,
“
AL
”
code in events memory.
Message
(2L)
Is merely displayed in the events menu as message
“
msg
”
.
Filter error
(3L)
Like function
|
1L
|
with fault message
“
Filter
”
Filter Message
(4L)
Like function
|
2L
|
with fault message
“
Filter
”
PINs
PIN
Function
PIN 0010
Opening service menu, if PIN-protection activated
PIN 1234
Freischalten Menu group
“
Setting
”
.
If
“
Set protection
”
=
“
ON
”
(see Controller Setup)
PIN 9090
Restore user setting
PIN 9091
Save user setting (corresponds function
“
Save user setup
”
=
“
ON
”
see Controller Setup)
PIN 9095
Restore factory setting = delivery status
Operating Instructions
UNIcon MODBUS Master
L-BAL-E255-GB 1901 Index 001
Part.-No.
110/121