5. Enter the last input to be added or removed from the group. If a single input is to
be edited then enter the same number as the first input.
EDIT GROUP 068
LOOP 01
INPUTS 015 TO 022
1=ADD, 2=REM, <=EXIT
6. Press 1 to add the inputs to the group or 2 to remove the inputs from the group. If
no changes are required press escape to exit. The menu will return to the group
allocation menu:
1=EDIT INPUT GROUPS
2=PRINT INPUT GROUPS
3=VIEW INPUT GROUPS
SELECT 1..3, <=EXIT
7. To view or print the input group allocation select option 2 or option 3.
24.24How To Edit The Expansion I/O Board Cause/effect
Each I/O board has 8 inputs and 8 outputs so board number 1 will have inputs 1 to 8
and outputs 1 to 8. Each output circuit has two channels associated with it, channel 0
and channel 1. If channel 0 is active then the output will be active continuously. If
channel 1 is active, the output will pulse for 1s on, 1s off. If both channel 0 and
channel 1 are active the output will be continuous.
The expansion I/O cause/effect is edited in exactly the same manner as the loop
output cause/effect. The steps are as follows:
Enter the engineer’s menu and select:
1:Panel set-up; 1:Input/output set-up; 2:Panel outputs; 2:Remote Output C/E
1. Enter the number of the output circuit to be edited.
2. The cause/effect for the output circuit is displayed
CAUSES FOR OP001 CH0
NO MORE CAUSES
>=OK,3=NX,4=+,<=EXIT
3. Either
i) Press > to save the data and move to the next output circuit or channel and
return to step 1.
ii) Press < to exit without saving changes to the current output.
iii) Press 3 to move to the next screen if more cause/effect is available. The
display will show NO MORE CAUSES if no more data is available.
iv) Press 4 to add more causes. The display is as follows:
CAUSES FOR OP001 CH0
1=GROUP CAUSE
2=COMMON CAUSE
SELECT 1..2, <=EXIT
Page 96 of 111