Written by: A.C. Amended by GG
Checked by: JBJ
Document Number: USDISC Rev.: 3
Page 16 of 47
19/07/2004
6.6 How To Enable Timed Sensitivity Mode.
1. Enter the user menu as described in section 6.
2.. Press 2 to select option. The following screen will be displayed:
PANEL MODES
1=PANEL DELAY
2=DAY/NIGHT
SELECT 1..2, <=EXIT
3. Press 2 to select option 2. The following screen will be displayed:
DAY/NIGHT MODE 2
1=DAY, 2=NIGHT,
3=TIMER, 4=OFF
<=EXIT
4. Display shows the night mode 2 selected, to select Timed mode press 3. The
following screen will be displayed.
DAY/NIGHT MODE 3
1=DAY, 2=NIGHT,
3=TIMER, 4=OFF
<=EXIT
5. Selecting the Timer option enables the active trip levels and sensitivity codes
depend upon the day of the week and the time.
6.7 How To Enable Off Sensitivity Mode.
1. Enter the user menu as described in section 6.
2. Press 2 to select option. The following screen will be displayed:
PANEL MODES
1=PANEL DELAY
2=DAY/NIGHT
SELECT 1..2, <=EXIT
3. Press 2 to select option 2. The following screen will be displayed:
DAY/NIGHT MODE 3
1=DAY, 2=NIGHT,
3=TIMER, 4=OFF
<=EXIT
4. Display shows the Timer mode 3 selected, to select the Off mode press 4. The
following screen will be displayed.
DAY/NIGHT MODE 4
1=DAY, 2=NIGHT,
3=TIMER, 4=OFF
<=EXIT
5. Selecting the Off option forces the active trip levels and sensitivity codes to their
Default value regardless of the time.