6. Enter the loop number of the devices to be added or removed from the zone and
press enter. The following screen is displayed if loop 1 is entered:
EDIT ZONE 07
LOOP 01
POINT? 001
>=ENTER, <=BACK
7. Enter the first device in a range to be added or removed from the zone. This
example shows device 15:
EDIT ZONE 07
LOOP 01
POINTS 015 TO 015
>=ENTER, <=BACK
8. Enter the last device to be added or removed from the zone. If a single device is to
be edited then enter the same number as the first device.
EDIT ZONE 07
LOOP 01
POINTS 015 TO 022
1=ADD, 2=REM, <=EXIT
9. Press 1 to add the devices to the zone or 2 to remove the devices from the zone. If
no changes are required press escape to exit. The menu will return to the zone
allocation menu:
1=EDIT POINT ZONES
2=PRINT POINT ZONES
3=VIEW POINT ZONES
SELECT 1..3, <=EXIT
24.9How To Print The Allocation Of Devices To A Zone
1. Enter the engineers menu as described in section 24.
2. Press 1 to select panel set-up. The following screen will be displayed:
1=LOOP SETUP
2=INPUT/OUTPUT SETUP
3=REPEATER SETUP
SELECT 1..2, <=EXIT
Page 86 of 111
02/10/03