24.
User Functions
To access the user menu perform the following operations:
1. Move the ACCESS CONTROLS lock switch to position 1 using the access
controls key.
2. Press 5 on the user controls to access the menu function. The following menu will
be displayed:
1 = USER MENU
ENTER ACCESS CODE
FOR ENGINEERS MENU
0000
3. Press 1 to enter the user menu. The following menu will be displayed:
1=TIME/DATE 2=MODES
3=EN/DIS 4=VIEW
5=TEST 6=PRINT
SELECT 1..6, <=EXIT
This is referred to as the user main menu screen and the description of the user
functions begin from this screen.
Note: The system automatically leaves the user menu after a period of time. This
automatic timeout prevents the system being left in the user or engineers access
mode unintentionally. The timeout period depends on the function selected and is
between 1 and 15 minutes.
23.1How To Enter Numbers
All menu selections are made using direct key access using keys 1 to 6.
Entry of digits is performed by the following method:
1. On entering a menu screen which requires a number to be entered a default
number will be displayed. For example when setting the time the current time is
displayed. The cursor will underline the first digit.
2. Press MENU UP or MENU DOWN to increment or decrement the digit.
3. When the digit is correct press > (ENTER) to move onto the next digit.
4. Press < to cancel the menu screen and move to the previous screen.
5. Change the remaining digits as required. On all but the first digit the < key moves
to the previous digit. When the cursor is positioned on the last digit pressing >
(ENTER) enters the value.
23.2How To Set The Time And Date
1. Enter the user menu as described in section 23.
2. Press 1 to select option 1. The screen will display the current date:
SET DATE? 30/05/99
>=ENTER VALUE
<=BACK/EXIT
Page 48 of 111
02/10/03
Silences the internal buzzer for
any condition
Silence fire events. If already
silenced re-activates the
previous alarm condition
Switch to 1 to enable controls
(enter level 2). Override delay
operates with switch in either
position.
Silences the internal buzzer for
any condition
User controls. Only
override delay is
available without
operating the access
controls keyswitch
User indications
20 character by 4 line
LCD display. Back-lit
when event present or
Access controls switch
ON.
Silence fire events. If already
silenced re-activates the
previous alarm condition