The panel can respond to either polarity on its power supply fault inputs. Note that
this is a factory configuration procedure that should not require changing by the
engineer.
To change the polarity enter the engineers menu and select:
1:Panel set-up; 2:input/output set-up; 4:Power Fault Polarity.
1. Press 1 to toggle the power fault polarity.
2. Press > to enter the new polarity or press < to escape without changing the power
fault polarity.
24.23How To Edit The Allocation Of Inputs To A Group
To change the expansion I/O board configuration enter the engineers menu and select:
1:Panel set-up; 2:Input/output set-up; 3:Panel output c/e;
1:Input group allocation; 1:Edit I/P groups.
1. The following screen will be displayed:
1=EDIT INPUT GROUPS
2=PRINT INPUT GROUPS
3=VIEW INPUT GROUPS
SELECT 1..3, <=EXIT
2. Press 1 to edit the point group allocation:
EDIT INPUT GROUPS
GROUP? 033
>=ENTER, <=BACK/EXIT
3. Enter the number of the group to be edited and press enter. The following screen
will be displayed if group 68 is entered:
EDIT GROUP 068
INPUT? 001
>=ENTER, <=BACK
4. Enter the first input in a range to be added or removed from the group. This
example shows input 15:
EDIT GROUP 068
LOOP 01
INPUT? 015
>=ENTER, <=BACK