Page 33 of 47
19/07/2004
5. Enter the number of the second input and press enter.
IDENTIFY INPUT RANGE
INPUTS 001 TO 002
1=ENABLE, 2=DISABLE
SELECT 1..2, <=EXIT
6. Choose the option required:
I) To enable the range of inputs displayed press 1
ii) To disable the range of inputs press 2
iii) To exit without making any changes press escape
The screen will display the previous page:
INPUT DISABLEMENT
1=SINGLE, 2=RANGE
3=VIEW
SELECT 1..3, <=EXIT
7. Press escape to exit the menu one level at a time.
6.28 How To Enable And Disable A Range Of Expansion Board Inputs
(Network Panel)
1. Enter the disablement menu as described in section 1.1.
EN/DIS:1=POINTS
2=ZONES, 3=PRINTER
4=SOUNDERS 5=INPUTS
6=OUTPUTS, <=EXIT
2. Press 5. The following screen will be displayed:
INPUT DISABLEMENT
1=SINGLE, 2=RANGE
3=VIEW
SELECT 1..3, <=EXIT
3. To disable a range of inputs press 2. The following screen will be displayed:
RANGE INPUTS EN/DIS
PANEL? 001
>=ENTER, <=BACK/EXIT
4. Enter the panel number and press enter to continue.
PAN001 INPUTS EN/DIS
INPUT? 001
>=ENTER, <=BACK/EXIT