Refer to Installation And Connection Of The A1620 Network Interface in
section 8.4.
9. Commission the network cause/effect (if applicable)
•
Refer to the
cause/effect
charts
•
Refer to Commissioning a Network System in section 9.5.3
6.General Description
The panels are housed in a single metal enclosure with a polyester membrane giving
user controls and indications. The mandatory indications are implemented using LEDs
and secondary information is provided by a 20 by 4 LCD. The standby batteries are
housed within the panel enclosure.
6.1Premier AL Panel Description
The panel consists of the modules shown in Figure 1. One loop card is fitted for each
loop that is connected to the panel. The Premier AL drives a maximum of four loops
of devices.
Figure 1 – Premier AL panel main components
6.1.1XP 150W-30-7 P.S.E.
The XP 150W is a switch mode p.s.e. providing a nominal 29.3V supply to the A1584
control board.
6.1.2A1584 P.S.E. Control Board
The A1584 is a processor controlled supply and generates the following outputs from
the 29.3V input:
•
5V regulated logic supply
•
28V supply to motherboard
Page 8 of 111
02/10/03
A1579 MOTHERBOARD (2500143)
A1584 PSE CONTROL BOARD (2500035)
A1599 PRINTER (2500107)
A1619 I/O INTERFACE (OPTIONAL 2500162)
A1619 REPEATER INTERFACE (OPTIONAL 2500162)
OR A1620 NETWORK INTERFACE (OPTIONAL 2500163)
A1580 DISPLAY BOARD (2500144)
XP 150W-30-7 PSU
UP TO 4 OFF A1585
LOOP CARD (2500130)