Notes:
1.
Use only RS485 shielded data cable.
2.
Do not connect the cable shield to earth.
REPEATER
A
D
DRESS
NE
TW
OR
K
1
S
1
4
2
8
U5
A
SCN
A
B SCN
B
A
J3
REPEATER
NETWORK
J6
J1
J5
X3
0V
28V
SCN FAULT
B
J4
I/O
U5
SCN
B
A
J3
NETWORK
J6
X3
FAULT
SCN
SCN
B
B
A
A
J4
I/O
28V 0V
A1620 NETWORK INTERFACE
FITTED TO A1579 MOTHERBOARD
FITTED TO A1579 MOTHERBOARD
A1620 NETWORK INTERFACE
2
1
3
4
2
1
3
4
2
1
S1
N
E
T
W
OR
K
A
DDR
E
SS
8
4
TO NEXT PANEL
Figure 4 – Network connection diagram
4. Set the network node address on the A1620 NETWORK ADDRESS switch as
shown Table 1. It should be noted that any number of panels can be configured as
address 0. This configures the panel as a passive node. A passive node can receive
data but cannot transmit data to other network panels.
5. To enable networking, S4 switch 4 on the A1579 should be moved to the ON
position (switch 2 on the A1638 Premier AL Global Repeater motherboard). This
should be done after stand-alone panel commissioning is complete.
Table 1 – A1620 node address switch settings
Page 18 of 111
02/10/03