APPENDIX F - Premier AL Global Network Repeater MechanicalAnd
Environmental Specification
Mechanical Specification
Size: Height:
Width:
Depth:
370mm
325mm
135mm including lock and indented holes
Weight excluding batteries:
7.4kg
Environmental Specification
Operating temperature:
-5ºC to 40ºC
Operating humidity:
5% to 95%
Mains Input Specification
Voltage:
230V AC +10%/-15%
Maximum Input Power:
120VA
Protection:
T3.15A anti-surge sand filled fuse
Cable requirements:
Minimum of 1mm
2
copper controlled by a 5A
fuse.
Power Supply Output Specification
24V output:
24V
±
0.5V @ 3A mains on
21-26V @ 3A mains failed
24V output protection:
Electronic current limiting
Common fault output:
Open collector output labelled FAULT
Battery Specification
Battery charger output:
float charger 27.5V
±
0.1V @ 1.5A maximum
Maximum battery load:
3A
Battery type:
2 off 12V 12Ah sealed lead acid standby
battery
Battery size:
151mm x 98mm x 97.5mm
Battery circuit protection:
3A fast blow glass fuse
Mains failed fault battery current:
1 Loop panel:
2 Loop panel:
120mA
140mA
Mains failed alarm battery current:
1 Loop panel:
2 Loop panel:
255mA
275mA
Page 108 of 111
02/10/03