PRINTING
LOOP 1 CONTENT
COMPLETE
<=EXIT
8. Press escape to exit the menu screen.
24.7How To Edit The Sensitivity Of A Point
The sensitivity of a point for both alert and fire conditions can be adjusted. For the
Fyreye sensors the analogue trip levels for alert and fire can be changed.
Note: For compliance with EN54 the fire sensitivity level must be set to 55. The pre-
alarm value can be set to any value
Note: Do not adjust the fire sensitivity level of the Fyreye high temperature heat
detector. This device has an analogue count of 55 at 90 C.
Note: Changing the sensitivity of a point only changes the current point sensitivity.
For example, changing the sensitivity of a point whilst the panel is in day mode
does not affect the sensitivity values of that point for the default or night mode
sensitivity.
24.8How To Edit The Allocation Of Devices To A Zone
1. Enter the engineers menu as described in section 24.
2. Press 1 to select panel set-up. The following screen will be displayed:
1=LOOP SETUP
2=INPUT/OUTPUT SETUP
3=REPEATER SETUP
SELECT 1..2, <=EXIT
3. Press 1, 2. The following screen will be displayed:
1=EDIT POINT ZONES
2=PRINT POINT ZONES
3=VIEW POINT ZONES
SELECT 1..3, <=EXIT
4. Press 1 to edit the point zone allocation:
EDIT ZONES
ENTER ZONE? 001
>=ENTER, <=BACK/EXIT
5. Enter the number of the zone to be edited and press enter. The following screen
will be displayed if zone 7 is entered:
EDIT ZONE 07
LOOP? 1
>=ENTER, <=BACK/EXIT
Page 85 of 111
02/10/03