Page – 38/75
AFMNA0AA – EPS-BLI HYG – User Manual
9.2.5
HARDWARE SETTINGS list
To enter this Zapi hidden menu a special procedure is required. Ask this procedure
directly to a Zapi technician.
U
Parameters in the HARDWARE SETTINGS list from 1 (ID RMS MAX) through 22
(AUX SPEED #1) are safety relevant and only well trained technicians are
allowed to change the default settings.
Figure 9.2.5-1.
1) ID RMS MAX
Ampere, 0 A through 255 A. Mandatory default value is 20 A.
Factory adjusted. This setting defines the maximum direct current in Arms.
2) MAX
FLUX
mWb, 0 mWb through 200 mWb. Default value is 83 mWb.
This setting defines the maximum linked flux (peak value) in the delta model.
Typically it is given by the formula 159 * Vbatt / corner freq. Not used.
3) KP1 DIVISOR IQSP
Number, 0 through 200. Mandatory default value is 16.
This setting defines the proportional divisor of the speed control. Factory adjusted.
4) KI1
IQSP
Number, 0 through 200. Mandatory default value is 10.
This setting defines the integral factor of the speed control. Factory adjusted.
KP1
KI1
KP2
KI2
KP3
KI3
ID RMS MAX
TR MILLISEC