FORM 150.63-NM6 (1020)
1
4. Put the unit into Service Mode (as described under
the Control Service and Troubleshooting section)
and cycle each condenser fan to ensure proper ro
tation.
5. Prior to this step, turn system 2 off (if applicable
–refer to Option 2 under “Unit Keys” section for
more information on system switches.) Connect a
manifold gauge to system 1 suction and discharge
service valves.
Place the Unit Switch in the control panel to the
ON position.
As each compressor cycles on,
ensure that the discharge pressure rises and
the suction pressure decreases.
If this does not
occur, the compressor being tested is operating
in the reverse direction and must be corrected.
After verifying proper compressor rotation, turn
the Unit Switch to “OFF.”
This unit uses scroll compressors
which can only operate in one direc-
tion. Failure to observe this will lead
to compressor failure.
6. YCUL0125 - YCUL0275 units only – Turn system
1 off and system 2 on (refer to Option 2 under
“UNIT KEYS” section for more information on
system switches.)
Place the Unit Switch in the control panel to the
ON position.
As each compressor cycles “on,”
ensure that the discharge pressure rises and
the suction pressure decreases.
If this does not
occur, the compressor being tested is operating
in the reverse direction and must be corrected.
After verifying proper compressor rotation, turn
the Unit Switch to “OFF.”
The Discharged Air or Suction Pres-
sure setpoint may need to be tempo-
rarily lowered to ensure all compres-
sors cycle “on.”
7. After verifying compressor rotation, return the
Unit Switch to the off position and ensure that
both Systems are programmed for “ON” (refer
to Option 2 under “Unit Keys” section for more
information on system switches).
INITIAL START-UP
After the preceding checks have been completed and
the control panel has been programmed as required in
the pre-startup checklist, the chiller may be placed into
operation.
1. Place the Unit Switch in the control panel to the
ON position.
2. The first compressor will start and a flow of refrig
-
erant will be noted in the sight glass. After several
minutes of operation, the vapor in the sight glass
will clear and there should be a solid column of
liquid when the TXV stabilizes.
OPTIONS
Display Language
Sys 1 Switch
Sys 2 Switch
* Ambient Control
Local/Remote Mode
Control Mode
Display Units
* Lead/Lag Control
* Fan Control
Manual Override
Current Feedback
** Soft Start
** Unit Type
** Refrigerant Type
** Expansion Valve Type
Must be in TXV Mode
SETPOINTS
Discharge Air or Suction Pressure
Range
EMS-PWM Max. Setpoint
PROGRAM
Discharge Pressure Cutout
* Suct. Pressure Cutout
Low Amb. Temp. Cutout
Anti-Recycle Time
* Fan Control On Pressure
* Fan Differential Off Pressure
Total # of Compressors
* Number of Fans/System
* Unit/Sys Voltage
Unit ID
* Sys 1 Superheat Setpoint
* Sys 2 Superheat Setpoint
TABLE 15 –
SETPOINTS ENTRY LIST
* NOT ON ALL MODELS
** VIEWABLE ONLY
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...