JOHNSON CONTROLS
129
FORM 150.63-NM6 (1020)
FIG. 20 –
MICROBOARD RELAY CONTACT
ARCHITECTURE
LD03842
The suction transducers have a range from 0 to 200
PSIG (13.79 BARG). The output will be linear from
.5VDC to 4.5VDC over the 200 PSIG (13.79 BARG)
range. Following is a formula that can be used to verify
the voltage output of the transducer. All voltage reading
are in reference to ground (unit case).
V = (Pressure in PSIG x .02) + .5
or
V = (Pressure in BARG x .29) + .5
where V = dc voltage input to micro
Pressure = pressure sensed by transducer
Following are the microboard connections for the Suc-
tion Transducer:
System 1 Suction Transducer
J4-5
= +5VDC
regulated supply to transducer.
J4-10
=
VDC
input signal to the microboard. See
the formula above for voltage readings that
correspond to specific suction pressures.
J4-1
= +5VDC
return
J4-2
= drain (shield connection = 0
VDC
)
System 2 Suction Transducer
J7-5
= +5VDC
regulated supply to transducer.
J7-10
=
VDC
input signal to the microboard. See
the formula above for voltage readings that
correspond to specific suction pressures.
J7-1
= +5VDC
return
J7-2
= drain (shield connection = 0
VDC
)
If the optional Suction Transducer is not used on the
YCUL0045 - YCUL0185 , a Low Pressure switch will
be used. Following are the microboard connections for
the Low Pressure switch.
System 1 Low Pressure Switch
J4-5
= +5VDC
regulated supply to LP switch.
J4-10
= input signal to the microboard. 0
VDC
=
open switch / +5VDC
= closed switch.
J4-2
= drain (shield connection = 0
VDC
)
System 2 Low Pressure Switch
J7-5
= +5VDC
regulated supply to LP switch.
J7-10
= input signal to the microboard. 0
VDC
= open
switch / +5VDC
= closed switch.
J7-2
= drain (shield connection = 0
VDC
)
DIGITAL OUTPUTS
Refer to the unit wiring diagram and Table 32. The dig-
ital outputs are located on TB3, TB4, and TB5 of the
microboard.
ALL OUTPUTS ARE 120VAC
with the
exception of TB5-3 to TB5-4. TB5-3 to TB5-4 are the
contacts that can be used for an evaporator pump start
signal. The voltage applied to either of these terminals
would be determined by field wiring.
Each output is controlled by the microprocessor by
switching 120VAC to the respective output connection
energizing contactors, evaporator heater, and solenoids
according to the operating sequence.
120VAC is supplied to the microboard via connections
at TB3-1, TB3-7, TB4-3, and TB4-7. Figure 23 illus-
trates the relay contact architecture on the microboard.
3
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...