![background image](http://html1.mh-extra.com/html/york/ycul0045/ycul0045_installation-operation-and-maintenance_4223634040.webp)
JOHNSON CONTROLS
40
FORM 150.63-NM6 (1020)
Installation
PHYSICAL DATA (ENGLISH)
YCUL0045 - YCUL0275
TABLE 13 –
PHYSICAL DATA (ENGLISH)
MODEL NUMBER YCUL
MODEL NUMBER YCUL00
0045
0061
0081
0095
0121
0125
0145
0161
0171
0185
0211
0235
0255
0275
General Unit Data
Nominal Tons, R-22
12.7
17.5
21.9
26.7
32.1
36.3
40.0
43.8
48.0
53.3
58.5
65.3
71.5
77.7
Nominal Tons, R-407C
12.2
16.9
21.3
26.0
31.2
35.1
38.9
42.6
46.8
52.3
56.5
63.3
69.6
75.8
Number of Refrigerant Circuits
1
1
1
1
1
2
2
2
2
2
2
2
2
2
Refrigerant Charge, Operating
R-22, ckt1 / ckt2, lbs
25.0
29.6
45.2
50.7
53.8
35.1/35.1
42.1/35.1
42.1/42.1
46.8/42.1
56.2/56.2
58.5/48.4
64.7/64.7
71.8/64.7
78.0/78.0
R-407C, ckt1 / ckt2, lbs
24.1
28.5
43.6
48.9
51.9
33.8/33.8
40.6/33.8
40.6/40.6
45.1/40.6
54.2/54.2
56.4/46.7
62.4/62.4
69.2/62.4
75.2/75.2
Pumpdown Capacity
R-22, ckt1 / ckt2, lbs
43.2
43.2
60.5
90.7
90.7
58.4/58.4
58.4/58.4
58.4/58.4
58.4/58.4
87.6/87.6
68.1/68.1
102.2/102.2
102.2/102.2
102.2/102.2
R-407C, ckt1 / ckt2, lbs
41.6
41.6
58.3
87.4
87.4
56.5/56.5
56.5/56.5
56.5/56.5
56.5/56.5
84.4/84.4
65.6/65.6
98.5/98.5
98.5/98.5
98.5/98.5
Oil Charge, ckt1 / ckt2, gallons
2.2
2.2
2.2
2.2
3.3
2.2/2.2
2.2/2.2
2.2/2.2
2.2/2.2
2.2/2.2
3.3/3.3
3.3/3.3
3.3/3.3
3.3/3.3
Operating / Shipping Weight
Aluminum Fin Coils, lbs
2051
2058
2401
2445
2788
3947
4000
4057
4114
4175
4842
5004
5150
5240
Copper Fin Coils, lbs
2201
2208
2551
2595
2938
4247
4300
4357
4414
4475
5142
5384
5530
5620
Compressors, Scroll Type
Compressors per circuit
2
2
2
2
3
2
2
2
2
2
3
3
3
3
Compressors per unit
2
2
2
2
3
4
4
4
4
4
6
6
6
6
Nominal Tons per compressor
7.5
10
13
15
13
10/10
13/10
13/13
15/13
15/15
13/10
13/13
15/13
15/15
Condenser
Total Face Area ft2
47.2
47.2
66.1
66.1
66.1
128.0
128.0
128.0
128.0
128.0
149.3
149.3
149.3
149.3
Number of Rows
2
2
2
3
3
2
2
2
2
3
2
3
3
3
Fins per Inch
13
13
13
13
13
13
13
13
13
13
13
13
13
13
Condenser Fans
Number of Fans total
2
2
2
2
2
4
4
4
4
4
4
4
4
4
Fan hp/kw
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.7
2 / 1.7
2 / 1.7
2 / 1.7
Fan RPM
950
950
950
950
950
950
950
950
950
950
950
950
950
950
Number of Blades
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Total Chiller CFM
16257
16257
23500
23500
23500
47360
47360
47360
47360
46080
55253
55253
54550
53760
Notes:
1. Operating Refrigerant Charge is for Condensing Units only. Does not include refrigerant lines and evaporator coil.
2. Pump Down Capacity is based on 100°F (37.8°C) liquid R22 and 80% of condenser volume.
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...